Teleinformation data explanation¶
You can find official ERDF informations here : http://www.erdf.fr/sites/default/files/ERDF-NOI-CPT_02E.pdf
Tag | Format | Description |
---|---|---|
ADCO | 12 car. | Electric meter address |
OPTARIF | 4 car. | Tariff option |
ISOUSC | 2 car. unit = ampere | Power subscribed |
BASE | 9 car. unit = Wh | Base option index |
HCHC | 9 car. unit = Wh | Peak hours index |
HCHP | 9 car. unit = Wh | Off peak hours index |
EJP HN | 9 car. unit = Wh | Normal hours index if option = EJP |
EJP HPM | 9 car. unit = Wh | Peak hours index if option = EJP |
PEJP | 2 car. | EJP notice (30 minutes before the period) if option = EJP |
BBR HC JB | 9 car. unit = Wh | Off peak hours index for blue days if option = tempo |
BBR HP JB | 9 car. unit = Wh | Peak hours index for blue days if option = tempo |
BBR HC JW | 9 car. unit = Wh | Off peak hours index for white days if option = tempo |
BBR HP JW | 9 car. unit = Wh | Peak hours index for white days if option = tempo |
BBR HC JR | 9 car. unit = Wh | Off peak hours index for red days if option = tempo |
BBR HP JR | 9 car. unit = Wh | Peak hours index for red days if option = tempo |
PTEC | 4 car. | Current tariff period |
DEMAIN | Tomorrow color if option = tempo | |
IINST | 3 car. unit = A | Instant power |
ADPS | 3 car. unit = A | Warning when the subscribed poower is reached (emmitted only when needed) |
IMAX | 3 car. unit = A | Maximum power |
PAPP | 5 car. unit = VA | Apparent power |
HHPHC | 1 car. | Hourly group |
MOTDETAT | 6 car. | Counter status |
Three phase specific data¶
If you have a 3-phase install, you will have more informations:
- iinst1, iinst2,iinst3 instead of iinst
- imax1, imax2, imax3 instaed of imax
If you use more power than provided on one phase, the information sent by teleinfo will change, and you will receive message using the schema teleinfo.short with only a few informations :
- ADIR1, ADIR2, ADIR3 : intensity overload on each phase
- IINST1, IINST2, IINST3 : intensity on each phase.